You are currently viewing our board as a guest which gives you limited access to view most discussions, articles and access our other FREE features. By joining our free community you will have access to searching the forum topics, post topics, communicate privately with other members (PM), respond to polls, upload your own photos and access many other special features. Registration is fast, simple and absolutely free so please, join our community today!

Heating

The is the forum to discuss general information regarding all Carver Yachts.
User avatar

Topic author United States of America
eburklo
Scurvy Dog
Scurvy Dog
Posts: 14
Joined: August 20th, 2013, 3:42 pm
Vessel Info: 2003 Carver 564

Heating

Postby eburklo » December 6th, 2013, 11:49 am

We own a 2003 Carver 564. Yacht has four ac/heat air handlers in the main cabin. All operate of a single raw water pump. We have two compressors in the engine room. Is it normal for the water pump and subsequently the compressors to come on only if the main salon is calling for heat. When the forward cabin and master cabin calls for heat, the compressor does not come on until the main salon compressor comes on.

User avatar

United States of America
waybomb
CYO Moderator
CYO Moderator
Posts: 2404
Joined: February 5th, 2013, 9:24 pm
Vessel Info: 1995 Boston Whaler Rage15
1987 3697 Carver Mariner
1988 Cougar 46 Kevlar Vee offshore
1969 15' Glasspar / 1967 Johnson Electromatic 85
1996 Boston Whaler Rage 15
Location: Saint Joseph,Mi
Has thanked: 50 times
Been thanked: 396 times

Re: Heating

Postby waybomb » December 6th, 2013, 5:35 pm

That does not sound correct. If any of the thermostats call for heat, the accompanying compressor as well as the common water pump should come on.
I would think the compressors would be separated from each other on their own thermostats.
It is common to have one pump; when either or both copmpressors run, the pump runs.
Thanks
Fred
1969 Glaspar Avalon /1969 Johnson Electromatic 85
1987 Carver Mariner
1988 Cougar Kevlar 46' with triple blown 572 ci
1995 Boston Whaler Rage
Past - 1988 2807, 1989 4207 Aft
User avatar

Topic author United States of America
eburklo
Scurvy Dog
Scurvy Dog
Posts: 14
Joined: August 20th, 2013, 3:42 pm
Vessel Info: 2003 Carver 564

Re: Heating

Postby eburklo » January 3rd, 2014, 2:20 pm

Crusair visited me last week. This is what we found.
The mail salon compressor does work as a ac/reverse heat unit and such the water pump kicks on appropriately when calling for heat or ac.
The bow bedroom and master bedroom compressor is not a reverse cycle unit. It only works to provide air conditioning. When in the heat mode, the master bedroom and bow bedroom have a coiled heating in the air handler. That is why I was getting heat and the compressor and raw water pump was not on.
User avatar

United States of America
waybomb
CYO Moderator
CYO Moderator
Posts: 2404
Joined: February 5th, 2013, 9:24 pm
Vessel Info: 1995 Boston Whaler Rage15
1987 3697 Carver Mariner
1988 Cougar 46 Kevlar Vee offshore
1969 15' Glasspar / 1967 Johnson Electromatic 85
1996 Boston Whaler Rage 15
Location: Saint Joseph,Mi
Has thanked: 50 times
Been thanked: 396 times

Re: Heating

Postby waybomb » January 3rd, 2014, 4:11 pm

So Carver installed resistance heating coils in the boat? Doesn't seem kosher. But it is what it is.
Thanks
Fred
1969 Glaspar Avalon /1969 Johnson Electromatic 85
1987 Carver Mariner
1988 Cougar Kevlar 46' with triple blown 572 ci
1995 Boston Whaler Rage
Past - 1988 2807, 1989 4207 Aft