buster53 wrote:Source of the post Easiest, cheapest way to go...just buy a 30 amp cord, cut off the female end and replace it with a new 125v-50 amp female end. Done.
It would work but i dont think its cheaper or better. since there are 2 50amp inlets imo as above it would be cheaper to purchase bulk cable from ebay etc whatever length you meed purchased by the foot. to make up short adapters and use the heavy oem cords he already has.rather than buying 2 30 cords already made up and cutting ends. To each their own. He also needs to decide if hes going to run 3 16k ac's cause they're going to pull more than 30 amps on that cord guaranteed. 405s has all acs on power 2 .





Do keep in mind you cannot get more than 60a out of dual 30a connections if using 125v. In comparison, running a single 250v 50a does supply the equivalent power of dual 125v 50a connections. I can now see why the 125v 50a was discontinued. Great discussion, learn something new every day.